Fire pump insights
This design guide is meant to provide code references and examples to help an electrical engineer determine basic criteria that must be met for the installation of a fire pump. This guide was developed from NFPA 20: Standard for the Installation of Stationary Pumps for Fire Protection (2019 edition) and NFPA 70: National Electrical Code Article 695 (2020 edition), and any information included is paraphrased. For complete definitions and information, see applicable code section. Please note: design could differ depending on jurisdiction requirements.
Electrical systems for fire pumps are governed specifically by NEC Article 695. This article includes all of requirements for normal and alternate sources of power for fire pumps. When having an alternate generator power source, it can be argued that it falls within the emergency branch in NEC Article 700 (from Informational Note), and by default under the life safety branch (which also points to NEC 700) when in a health care facility under NEC Article 517.
Figure 1: Design process for configuring electrical service to a fire pump. Courtesy: Affiliated Engineers Inc.
Coordinate with the fire protection engineer to determine pump requirements. The normal source must be in accordance with one of the following (NEC Article 695.3):
The normal source must be deemed reliable and able to carry the LRCs of the fire pump motor and the pressure maintenance pumps and the full load current (FLC) of the accessory equipment. If this isn’t met, an alternate source is needed.
A reliable source possesses the following characteristics, but is up to the authority having jurisdiction (AHJ) to determine (per NFPA 20: Standard for the Installation of Stationary Pumps for Fire Protection Article A9.3.2):
An alternate source of power must be one of these scenarios (NFPA 20 Article 9.3.4):
When one of the sources is a dedicated feeder derived from a utility service and separate from the normal source, the disconnecting means, OCPD and conductors are not required to meet NFPA 20 Article 9.2 and shall be permitted to be installed with NFPA 70 (NFPA 20 Article 9.3.6.1)
Protective devices cannot be installed on load side of the power transfer switch (NFPA 20 Article 9.3.6.2).
Figure 2: Arrangement A single line provides possible preferred source configuration for fire pump fed from a utility-owned transformer. Arrangement B single line provides possible preferred source configuration for fire pump fed from a separate service. Courtesy: Affiliated Engineers Inc.
The following are the steps that must be taken to receive approval from the AHJ:
Preferred source arrangement examples are shown in Figures 2 and 3. Alternate source arrangement examples are shown in Arrangement A, and Arrangement B.
Jockey pumps are also known as a pressure-maintenance pump. These keep the pressure in the system at a constant level when fire pump is not in use. Note: Jockey pumps cannot be fed from downstream of the fire pump controller.
The jockey pump can be connected in multiple ways:
The best way to provide continuity of reliable power is a direct connection of the source to the fire pump control equipment. However, additional disconnects are permitted to create an electrically safe work condition and may be required by facility management.
The number of disconnecting means permitted are based on NEC Article 695.4(B)(1) and 695.5(B)].
Fire pump controller
Fire pump transfer switch
Combination fire pump controller and transfer switch
Note: For an individual normal feed, if there is an OCPD in the disconnecting means, it must be capable of carrying the LRC on the normal side.
To provide one disconnecting means before the fire pump, it must comply with NFPA 20 Article 9.2.3.1:
Note: “Sufficiently remote” is not defined by the NEC. How this is achieved needs to be acceptable to the AHJ.
Supervision in closed position by one of the following (NEC Article 695.4(B)(3)):
Controllers shall be equipped with contacts (open or closed) to operate circuits for four conditions (NFPA 20 Article 10.4.8):
When a transfer switch is used, two additional contacts are required for following conditions:
Note: Remember to coordinate short circuit current ratings for the controller and soft starter or variable frequency drive when tied to a generator.
Figure 3: Arrangement C provides possible preferred source configuration for fire pump fed from tap ahead of the main on a double-ended substation. Configuration to be similar for single-ended substation. Courtesy: Affiliated Engineers Inc.
Starting voltage drop: Shall not be more than 15% at motor-starting conditions unless (NEC Article 695.7(A)):
Running voltage drop: Shall not drop more than 5% when motor is operating at 115% of the FLC rating (NEC Article 695.7(B)).
Note: Voltage drop can be calculated using an electrical software program, such as SKM System Analysis Inc., or done by default on generator vendor sizing programs.
Note: 15% needs to be maintained even when the generator is running, serving all other loads and then the fire pump is called to start.
Figure 4: Arrangement A provides possible alternate source configuration for fire pump fed directly from generator circuit breaker. Arrangement B provides possible alternate source configuration for fire pump fed from generator switchboard. Courtesy: Affiliated Engineers Inc.
Fire pump alarm and signals shall indicate (NFPA 20 Article 10.4.7.2):
Affiliated Engineers Inc. is a CFE Media content partner.
Do you have experience and expertise with the topics mentioned in this content? You should consider contributing to our WTWH Media editorial team and getting the recognition you and your company deserve. Click here to start this process.