Back to basics: Fire pump electrical design guide

This quick reference offers a guide for fire pump electrical design

By Rachel Stencel November 21, 2022

Courtesy: Affiliated Engineers Inc.

Learning Objectives

Fire pump insights

This design guide is meant to provide code references and examples to help an electrical engineer determine basic criteria that must be met for the installation of a fire pump. This guide was developed from NFPA 20: Standard for the Installation of Stationary Pumps for Fire Protection (2019 edition) and NFPA 70: National Electrical Code Article 695 (2020 edition), and any information included is paraphrased. For complete definitions and information, see applicable code section. Please note: design could differ depending on jurisdiction requirements.

Electrical systems for fire pumps are governed specifically by NEC Article 695. This article includes all of requirements for normal and alternate sources of power for fire pumps. When having an alternate generator power source, it can be argued that it falls within the emergency branch in NEC Article 700 (from Informational Note), and by default under the life safety branch (which also points to NEC 700) when in a health care facility under NEC Article 517.

Figure 1: Design process for configuring electrical service to a fire pump. Courtesy: Affiliated Engineers Inc.

Determine fire pump power source

Coordinate with the fire protection engineer to determine pump requirements. The normal source must be in accordance with one of the following (NEC Article 695.3):

Determine reliability/alternate source

The normal source must be deemed reliable and able to carry the LRCs of the fire pump motor and the pressure maintenance pumps and the full load current (FLC) of the accessory equipment. If this isn’t met, an alternate source is needed.

A reliable source possesses the following characteristics, but is up to the authority having jurisdiction (AHJ) to determine (per NFPA 20: Standard for the Installation of Stationary Pumps for Fire Protection Article A9.3.2):

An alternate source of power must be one of these scenarios (NFPA 20 Article 9.3.4):

When one of the sources is a dedicated feeder derived from a utility service and separate from the normal source, the disconnecting means, OCPD and conductors are not required to meet NFPA 20 Article 9.2 and shall be permitted to be installed with NFPA 70 (NFPA 20 Article 9.3.6.1)

Protective devices cannot be installed on load side of the power transfer switch (NFPA 20 Article 9.3.6.2).

Figure 2: Arrangement A single line provides possible preferred source configuration for fire pump fed from a utility-owned transformer. Arrangement B single line provides possible preferred source configuration for fire pump fed from a separate service. Courtesy: Affiliated Engineers Inc.

Receiving AHJ approval

The following are the steps that must be taken to receive approval from the AHJ:

  1. Need reliability report from the utility on multiple years of history.
  2. Written formal statement and saved in the project directory.
  3. Presented to the AHJ and client early in the project.

Electrical configurations

Preferred source arrangement examples are shown in Figures 2 and 3. Alternate source arrangement examples are shown in Arrangement A, and Arrangement B.

Jockey pumps are also known as a pressure-maintenance pump. These keep the pressure in the system at a constant level when fire pump is not in use. Note: Jockey pumps cannot be fed from downstream of the fire pump controller.

The jockey pump can be connected in multiple ways:

Disconnect requirements

The best way to provide continuity of reliable power is a direct connection of the source to the fire pump control equipment. However, additional disconnects are permitted to create an electrically safe work condition and may be required by facility management.

The number of disconnecting means permitted are based on NEC Article 695.4(B)(1) and 695.5(B)].

Fire pump controller

Fire pump transfer switch

Combination fire pump controller and transfer switch

Note: For an individual normal feed, if there is an OCPD in the disconnecting means, it must be capable of carrying the LRC on the normal side.

To provide one disconnecting means before the fire pump, it must comply with NFPA 20 Article 9.2.3.1: